R-454B Pressure-Temperature Chart
R-32 / R-1234yf (68.9% / 31.1% by mass). Standard saturation pressures across evaporator, suction, and condensing temperatures.
Nominal Glide: about 2.5 °F (1.5 °C) at typical evaporator and condenser conditions
R-454B is a zeotropic blend with temperature glide of about 2.5 °F (1.5 °C) at typical evaporator and condenser conditions. When measuring subcooling on the liquid line, use the bubble saturation column. When measuring superheat on the suction line, use the dew saturation column.
psig = psia − 14.696 (standard atmospheric pressure at sea level). At higher elevations, adjust gauge manifold readings accordingly.