Superheat & Subcooling Calculator
Quickly calculate actual superheat and subcooling for R-454B, R-32, R-410A, R-404A, R-448A, and R-507A HVAC and refrigeration equipment. Uses dew saturation for vapor superheat and bubble saturation for liquid subcooling.
Suction Line Superheat
Uses Dew PointMeasured at the suction line service valve near the outdoor unit (or evaporator outlet).
Liquid Line Subcooling
Uses Bubble PointMeasured at the liquid line service valve leaving the outdoor condenser coil.
How Superheat and Subcooling Work
Superheat measures how many degrees a refrigerant vapour is heated above its saturation (boiling) temperature after completely evaporating. It ensures liquid refrigerant does not flood back into the compressor. On systems with a thermal expansion valve (TXV), superheat is regulated automatically.
Subcooling measures how many degrees liquid refrigerant is cooled below its saturation (condensing) temperature after completely condensing. It ensures a pure liquid column reaches the metering device without vapour flash gas. TXV-metered systems are typically charged by subcooling.
Zeotropic refrigerant glide (R-454B & R-448A): Because zeotropic blends boil and condense across a range of temperatures (such as R-454B with ~2.5 °F glide and R-448A with ~9.5 °F glide), you must use the dew point for superheat (vapour state) and the bubble point for subcooling (liquid state). For pure R-32 and near-azeotropic R-410A and R-507A, the bubble and dew points are identical (or effectively identical).
psig = psia − 14.696 (standard atmospheric pressure at sea level).